  • RELAY
  • rms MATRIX 2SYS212S syncronising chek Relay
rms MATRIX 2SYS212S syncronising chek Relay

rms MATRIX 2SYS212S syncronising chek Relay

Update Terakhir 10 / 01 / 2024
Minimal Pembelian 1 Unit

Harga

CALL
Bagikan
DESKRIPSI PRODUK

Detail Rms MATRIX 2SYS212S Syncronising Chek Relay

Relay Module

Features
SYSTEM FEATURES
◼ Large back lit display panel
◼ System status LED indicators
◼ Simple menu setting procedure
◼ Wide auxiliary supply range with
fail alarm contact
◼ Self diagnosis & fail alarm
◼ Size 4M56-S draw out case
◼ Made in Australia
CONTROL FEATURES
◼ Synchronism Check (25)
◼ Adjustable phase angle and time
delay
◼ Flexible Live and Dead Voltage
configuration
◼ Bus or Line U/V Close Block
◼ Voltage Differential Close Block
◼ Frequency Slip Close Block
◼ Flexible Synchronism Check
Bypass Logic
◼ Manual Safe to Close Feature
METERING
◼ Line & Bus voltage display
◼ Relative phase angle display
◼ Line & Bus frequency display
◼ Frequency slip display
COMMUNICATION
◼ USB front programming port
◼ Non platform specific PC
programming software:
MATRIXwin
◼ Optically isolated RS485 network
communication port
◼ MODBUS RTU compatible network
protocol
Technical Bulletin 2SY212-S
Synchronism Check Relay
2SY212-S depicted in a 4M56-S draw out case
Description Made in Australia
The 2SY212 synchronism check relay is designed to measure the phase angle between the
monitored single phase voltages on the line & bus sides of a circuit breaker & verify that this
angle is less than setting. If the measured angle has met this criteria for the time period defined
by the setting & the voltage magnitudes meet the criteria established by the Live Line/Bus &
U/V Line/Bus settings, the output relay will be energised & the breaker permitted to close.
Resetting will occur if either the phase angle or voltage magnitude stray outside the pre-set
limits or if the sync check enable input is de-energised. Front panel LED's provide visual
indication of relay status & sync check function.
Bus or Line U/V, Differential Voltage and Frequency Slip Close block functionality together with
flexible synchronism check bypass logic caters for a diverse range of applications.