  • Woodward Easygen 1000
Woodward Easygen 1000

Woodward Easygen 1000

Update Terakhir 01 / 12 / 2019
Minimal Pembelian 1 Unit

Harga

CALL
Bagikan
DESKRIPSI PRODUK

Detail Woodward Easygen 1000

A pplication Notes Starting Firmware V1.0016 Rated Voltage / Frequency Mains aaaaaaaaaaaaaaaaaaaaaaaaa The proportional values for emergency mode relate to the generator nominal voltage. The mains has no own pa-rameters yet ( implemented in V1.0017) . Rated Voltage Generator aaaaaaaaaaaaaaaaaaaaaaaaa The generator rated voltage relates to the secondary values of the generator voltage transformer. Since V1.0017 it relates to the primary values! Close GCB in MANUAL Mode aaaaaaaaaaaaaaaaaaaaaaaaa The generator undervoltage monitoring level 1 and 2 must be enabled to close the GCB in MANUAL mode. Emergency Mode aaaaaaaaaaaaaaaaaaaaaaaaa When the mains return after a mains failure and the DI release MCB is disabled, the GCB will stay closed as long as the mains settling time is active. After that the GCB will open and the generator will shutdown. To prevent a dead busbar the unit needs a signal for " Start req. in AUTO" , see also Test With Load on page 18. ©